Disconnect load from slack

In this example, we examine the voltage transient of the system after a single load of constant P is isconnected from a slack.

using EMTSim
using BlockSystems
using ModelingToolkit
using NetworkDynamics
using Graphs
using OrdinaryDiffEq
using DiffEqCallbacks
using SteadyStateDiffEq
using Plots
using Unitful
using CSV
using DataFrames

Constants and unit stuff.

ω0    = 2π*50u"rad/s"
Sbase = 300u"MW"
Vbase = 110u"kV" #* sqrt(2/3)
Ibase = Sbase/(Vbase )#* √3) # why the √3 ?
Cbase = Ibase/Vbase
Lbase = Vbase/Ibase
Rbase = (Vbase^2)/Sbase

Rline = 1u"Ω" / Rbase           |> u"pu"
Pload = -300u"MW" / Sbase       |> u"pu"
Rload = (1u"pu")^2 / Pload      |> u"pu" # R=U^2/P
Cline = (2e-6)u"F" / Cbase      |> u"s"
Lline = (1/100π)u"H" / Lbase    |> u"s"

Slack Bus

The slack bus is modelld as a node with $\dot(u) = 0$, i'll keep the initial voltage forever.

@variables t u_d(t) u_q(t)
dt = Differential(t)

slackblock = IOBlock([dt(u_d) ~ 0, dt(u_q) ~ 0], [], [u_d, u_q]; name=:slack)
IOBlock :slack with 2 eqs
  ├ inputs:  (empty)
  ├ outputs: u_d(t), u_q(t)
  ├ istates: (empty)
  └ iparams: (empty)

create ODE Vertex from this block

slack = ODEVertex(slackblock)

Constant R Load

I tried to model an constan R load first using the algebraic current equation

\[i = -\frac 1 R \, u\]

This however, did not match the powerfactory results. The power factory load is purely ohmic (no phase shift) but constant in P. Since the voltage on bus 2 is slighly below 1 pu, we can not trivially calculate the corresponding resistance.

@variables t i_d(t) i_q(t)
@parameters u_d(t) u_q(t) R
loadblock = IOBlock([i_d ~ -1/R * u_d,
                     i_q ~ -1/R * u_q],
                    [u_d, u_q], [i_d, i_q],
                    name=:load)

# The load is used as a current source in a `BusBar`
busblock = BusBar(loadblock; name=:loadbus)
busblock = set_p(busblock, Dict(:C=>ustrip(u"s", Cline), :ω0=>ustrip(u"rad/s", ω0)))

# The `BusBar` block can be used to create an ODE Vertex
load = ODEVertex(busblock, [:load₊R])

Constant P Load

For a constant load P we may use the algebric current equation

\[i_d = P \frac{u_d}{u_d^2 + u_q^2}\\ i_q = P \frac{u_q}{u_d^2 + u_q^2}\]

However, this leads to instability in the model and is hard to initialize. I guess it is not a good idea to follow each oszillation in node/condensator voltage!

To circumvent the problem, we model the P load using a lowpass filter

\[\dot{i_d} = \frac{1}{\tau}\left(P \frac{u_d}{u_d^2 + u_q^2} - i_d\right)\\ \dot{i_q} = \frac{1}{\tau}\left(P \frac{u_q}{u_d^2 + u_q^2} - i_q\right)\]

whose time constant $\tau = \frac{1}{\omega_0}$ is chosen in a way, that disturbances higher than the nominal grid frequency are damped.

@variables t i_d(t) i_q(t)
@parameters u_d(t) u_q(t) P τ
loadblock = IOBlock([dt(i_d) ~ ustrip(u"rad/s", ω0)*(P * u_d/(u_d^2 + u_q^2) - i_d),
                     dt(i_q) ~ ustrip(u"rad/s", ω0)*(P * u_q/(u_d^2 + u_q^2) - i_q)],
                    [u_d, u_q], [i_d, i_q],
                    name=:load)
IOBlock :load with 2 eqs
  ├ inputs:  u_d(t), u_q(t)
  ├ outputs: i_d(t), i_q(t)
  ├ istates: (empty)
  └ iparams: P

The load is used as a current source in a BusBar

busblock = BusBar(loadblock; name=:loadbus)
busblock = set_p(busblock, Dict(:C=>ustrip(u"s", Cline), :ω0=>ustrip(u"rad/s", ω0)))
IOBlock :loadbus with 4 eqs
  ├ inputs:  i_d(t), i_q(t)
  ├ outputs: u_d(t), u_q(t)
  ├ istates: load₊i_d(t), load₊i_q(t)
  └ iparams: load₊P

The BusBar block can be used to create an ODE Vertex

load = ODEVertex(busblock, [:load₊P])
┌ Warning: The ordering of the states might change in future versions. Therefore it is highly recommend to provide all variables in the f_* arguments. There are missing entrys in f_states are missing some entrys!
└ @ BlockSystems ~/.julia/packages/BlockSystems/2Wytv/src/function_generation.jl:85

ODE edge for the RL Line

@variables t i_d(t) i_q(t)
@parameters u_d_src(t) u_q_src(t) u_d_dst(t) u_q_dst(t) R L ω

lineblock = IOBlock([dt(i_d) ~  ω * i_q  - R/L * i_d + 1/L*(u_d_src - u_d_dst),
                     dt(i_q) ~ -ω * i_d  - R/L * i_q + 1/L*(u_q_src - u_q_dst)],
                    [u_d_src, u_q_src, u_d_dst, u_q_dst],
                    [i_d, i_q],
                    name=:RLLine)
lineblock = set_p(lineblock, Dict(:R=>NoUnits(Rline), :L=>ustrip(u"s", Lline), :ω=>ustrip(u"rad/s", ω0)))
IOBlock :RLLine with 2 eqs
  ├ inputs:  u_d_src(t), u_q_src(t), u_d_dst(t), u_q_dst(t)
  ├ outputs: i_d(t), i_q(t)
  ├ istates: (empty)
  └ iparams: (empty)

This block can be used to create an ODEEdge

edge = ODEEdge(lineblock)

Set up the network

g = SimpleGraph(2)
add_edge!(g, 1, 2)
nd = network_dynamics([slack, load], edge, g)

We use SteadyStateDiffeq to find the steady state based on an initial guess. The initial guess just contains voltage at both nodes. The load value is given as a parameter to node 2.

uguess = zeros(length(nd.syms))
uguess[[1,3]] .= 1.0 # set the d component of the slack to 1 from the beginning
p = ([0, NoUnits(Pload)], nothing)
ssprob = SteadyStateProblem(nd, uguess, p)
u0 = solve(ssprob, DynamicSS(AutoTsit5(Rosenbrock23())))
┌ Warning: Interrupted. Larger maxiters is needed. If you are using an integrator for non-stiff ODEs or an automatic switching algorithm (the default), you may want to consider using a method for stiff equations. See the solver pages for more details (e.g. https://diffeq.sciml.ai/stable/solvers/ode_solve/#Stiff-Problems).
└ @ SciMLBase ~/.julia/packages/SciMLBase/byoKQ/src/integrator_interface.jl:352

Let's ignore this warning for now. I am not sure why the steady state is not completly steady. it nearly is.

Simulation

We simulate a disconnection of the load at t=0.1 s. This is done using a callback. The callback does 2 things: it sets the reference point P to zero, it sets the currents flowing through the load to zero.

tspan = (0.0, 0.124)
affect = function (integrator)
    integrator.p = ([0, 0.0], nothing)
    integrator.u[[5,6]] .= 0.0
end
cb = PresetTimeCallback(0.1, affect)
prob = ODEProblem(nd, u0, tspan, p; callback=cb)
sol = solve(prob, Tsit5(),dtmax=0.00001)

We may now transformation the results back to a,b,c frame

a,b,c = Tdqinv(sol.t, sol[3,:], sol[4,:])

Comparison with power factory results

Read the Power Facory data and plot for reference

$V_{base}$ is RMS phase-phase voltage.

\[V_{star} = \frac{1}{\sqrt{3}} * V_{base}\\ \hat{V} = \sqrt{\frac{2}{3}} * V_{base}\]

Therefore, i have to multiply the a, b and c results by sqrt(3/2)

df = CSV.read(joinpath(dirname(pathof(EMTSim)), "..", "data","PowerFactory", "Test_EMT.csv"), DataFrame, skipto=3,
              header=[:t, :u_1_a, :u_1_b, :u_1_c, :u_2_a, :u_2_b, :u_2_c])

xlims = (0.099,0.124)
plot(df.t, df.u_2_a; label="PowerFactory A", xlims, color=:lightgray,  linewidth=5)
plot!(sol.t, a.*sqrt(3/2); label="u_2_a", xlims)

plot!(df.t, df.u_2_b; label="PowerFactory B", color=:lightgray, linewidth=5)
plot!(sol.t, b.*sqrt(3/2); label="u_2_b")

plot!(df.t, df.u_2_c; label="PowerFactory C", color=:lightgray, linewidth=5)
plot!(sol.t, c.*sqrt(3/2); label="u_2_c")

In this graph, the PowerFactory solution is light gray and thick behind our solution.

... lets have a closer look

xlims!(0.0995,0.105)